| FireVoice-25/50 |
Small applications |
| Single channel audio |
| |
|
| Standard Features |
| Integral 25 watt, 25 VRMS audio amplifier with single Style
Z (Class A) or Style Y (Class B) speaker circuit (expandable to 50 watts using the ACC-AAM25). |
| Modular design for maximum system flexibility and ease of service. |
| Five Command Input Circuits (CMD) are available for activation by an FACP. |
| Two command input circuits can be independently fieldprogrammed
for activation by a Notification Appliance Circuit (NAC) or contact closure. |
| Three command input circuits activate on contact closure |
| Manual deactivation of speaker zones. |
| Command inputs allow: |
| |
One 60-second message. |
| Two 30-second messages. |
| Three 20-second messages. |
| Four 15-second messages. |
| Five 12-second messages. |
| Microphone time-out feature. |
| Nineteen different system and diagnostic LEDs. |
| Two Form-C trouble relays (System & AC Power Loss). |
| Optional equipment: second amplifier; local playback speaker; and remote microphone. |
| Integral digital message generator with standard, factory prerecorded emergency evacuation message. |